When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction.
Malfunction Caused
Indoor heat exchanger (pipe) thermistor
4-way valve malfunction
Troubleshooting
When abnormality starts again
↓
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Check the indoor pipe temperature thermistor:
• Plug out connector (CN-TH) from the indoor unit PCB
• Measure the resistance of the indoor heat exchanger temperature thermistor
↓
Is the measured resistance of the indoor pipe temperature thermistor matches the value specified in its characteristic chart?