During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal.
Malfunction Caused
Faulty indoor unit PCB.
Faulty outdoor unit PCB.
Indoor unit-outdoor unit signal transmission error due to wiring error.
Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.
Troubleshooting
When abnormality indication starts again
↓
Measure the AC voltage at terminal 1 & 2 of outdoor unit terminal board
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
↓
Is the measured voltage 230/240V?
NO →
AC power supply abnormal fluctuation
YES
↓
Measure the DC voltage at terminal 2 & 3 (communication terminals) of outdoor unit terminal board
↓
Is the measured DC voltage fluctuate between 10~70V? (Value depend on multimeter accuracy)
NO →
Defect in communication circuitry of outdoor unit PCB
Replace the PCB
YES
↓
Measure the AC voltage at terminal 1 & 2 of indoor unit terminal board
↓
Is the measured voltage 230/240V?
NO →
Improper connection at terminals indoor/outdoor
Check indoor/outdoor connecting cable
YES
↓
Measure the DC voltage at terminal 2 & 3 of indoor unit terminal board
↓
Is the measured DC voltage fluctuate between 10~70V?
NO →
Improper connection at terminals indoor/outdoor
Check indoor/outdoor connecting cable
YES
YES ↓
→
Defect in receiver/transmitter module of the communication circuitry in indoor unit PCB