During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
↓
Check the connector connection:
• Plug out connector from the indoor unit PCB
• Measure the resistance of the indoor pipe temperature sensor
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
↓
Is the connector connection normal?
NO →
Connector poor contact
Correct the connection
YES
↓
Check the indoor air temperature sensor:
• Plug out connector from the indoor unit PCB
• Measure the resistance of the indoor intake air temperature sensor
↓
Is the measured resistance of the indoor intake air temperature sensor matches the value specified in its characteristic chart?