Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation.
Phenomena: unit is stopping and re-starting very often in heating mode
Malfunction Caused
Indoor heat exchanger thermistor
Clogged air filter or heat exchanger
Over-bent pipe (liquid side)
Troubleshooting
When abnormality indication starts again
↓
Check the indoor unit intake air filter
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
↓
Is the air filter dirty?
YES →
Clean the air filter
NO
↓
Check the dust accumulation on the indoor unit heat exchanger
↓
Is the indoor unit heat exchanger dirty?
YES →
Clean the indoor unit heat exchanger
NO
↓
Check the indoor pipe temperature thermistor:
• Plug out connector (CN-TH) from the indoor unit PCB
• Measure the resistance of the indoor heat exchanger temperature thermistor
↓
Is the measured resistance of the indoor pipe temperature thermistor matches the value specified in its characteristic chart?